16 • 35-3000RK-LEL/O Sample-Draw Detector
Calibration, Combustible Sensor
This section describes how to calibrate the combustible sensor in the sample-draw
detector. It includes procedures to prepare for calibration, set the zero reading, set the
response reading, and return to normal operation.
The standard calibration gas for the sample-draw detector is methane. The sample-draw
detector may be calibrated to other combustible gases such as hexane or hydrogen. Use
the correct calibration gas for your installation.
NOTE: Calibrating the sample-draw detector may cause alarms. Be sure to put the
controller into its calibration program or disable external alarms before
continuing.
NOTE: This procedure describes calibration using a demand flow regulator.
Preparing for Calibration
NOTE: If you can verify a fresh air environment, it is not necessary to use the zero air
calibration cylinder to set the zero reading.
1. Follow the instructions in the controller’s operator’s manual for entering calibration
mode.
2. Screw the regulator into a zero air calibration cylinder.
Setting the Zero Reading
1. Connect the sample tubing from the demand flow regulator to the sample-draw
detector’s inlet line. This step is not necessary if you verified a fresh air
environment earlier in this procedure.
2. Allow the sample-draw detector to draw sample for one minute.
3. Follow the directions in the controller’s operator’s manual for setting the zero
reading. If you used a zero air calibration cylinder to set the zero reading, proceed to
step 4. If you verified a fresh air environment, proceed to the next section, Setting the
Response Reading.
4. Disconnect the sample tubing from the inlet line.
5. Unscrew the regulator from the zero air calibration cylinder.
Setting the Response Reading
1. Screw the regulator into the combustible gas calibration cylinder.
2. Connect the sample tubing from the demand flow regulator to the sample-draw
detector’s inlet line.
3. Allow the sample-draw detector to draw sample for one minute.
4. Follow the directions in the controller’s operator’s manual for setting the span.
5. Disconnect the sample tubing from the inlet fitting.
6. Unscrew the regulator from the combustible gas calibration cylinder.